Anti-Oxidant Code Question

Published by Don Hester on

This is a question that come up from time time. For aluminum conductors is Anti-Oxidant grease required on the terminations?

A- Yes

B- No


For the answer we refer to section 110.14 of the NEC

110.14 – Electrical Connections

Because of different characteristics of dissimilar metals, devices such as pressure terminal or pressure splicing connectors and soldering lugs shall be identified for the material of the conductor and shall be properly installed and used. Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors (such as copper and aluminum, copper and copper-clad aluminum, or aluminum and copper-clad aluminum), unless the device is identified for the purpose and conditions of use. Materials such as solder, fluxes, inhibitors, and compounds, where employed, shall be suitable for the use and shall be of a type that will not adversely affect the conductors, installation, or equipment.

So the last line from 110.14 states.- “Materials such as solder, fluxes, inhibitors, and compounds, where employed, shall be suitable for the use and shall be of a type that will not adversely affect the conductors, installation, or equipment.” So if you use it it must suitable for the use and adversely affect the connection. But it does not require it to be used.


From Paul Abernathy-

“Oxidation at the termination is undesired so the aluminum association provides guidance on preparation of all terminations but also fully understand that most manufacturers of lugs or lugs used in their equipment are tested without such compounds.

We acknowledge that but by encouraging the use at terminations can increase longevity. Half the time people do not torque as they should which can increase contact resistance at the termination and increase issues down the road that we may not experience if they did torque them properly. The anti-oxidation compounds can help reduce oxidation at these vital points but manufactures of wire and cable leave that to the other product manufacturers”

If you find any errors or have additional information that would expand on any code, building standards or manufacturer requirements please let me know.

NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

Coordinator & Instructor- Fundamentals of Home Inspection-  Bellingham Technical College

Former WA Home Inspector Advisory Licensing Board

www.ncwhomeinspections.com                                                   509-670-9572

 You can follow me on Facebook, Twitter, Google+ and on my website Blog.

 


If you find any errors or have additional information that would expand on any code, building standards or manufacturer requirements please let me know.

NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

Coordinator & Instructor- Fundamentals of Home Inspection-  Bellingham Technical College

Former WA Home Inspector Advisory Licensing Board

www.ncwhomeinspections.com                                                   509-670-9572

 You can follow me on Facebook, Twitter, Google+ and on my website Blog.

 


    

(Click on Icons to go to social media pages.)